Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

공기열원 히트펌프의 난방 성능특성에 관한 실험적 연구Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type

Other Titles
Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type
Authors
이권재권영철전종균박삼진권정태허철
Issue Date
31-10월-2011
Publisher
대한설비공학회 설비공학논문집
Keywords
Air to water; COP; Heating capacity; Heat pump; Performance
Citation
설비공학논문집, v.23, no.6, pp 400 - 405
Pages
6
Journal Title
설비공학논문집
Volume
23
Number
6
Start Page
400
End Page
405
URI
https://www.kriso.re.kr/sciwatch/handle/2021.sw.kriso/7913
Abstract
This paper presents the heating performance characteristics of the air source heat pump with air to water type. The heating capacity, COP, P-h diagram were measured at various operating conditions, air-side temperatures, relative humidities, and inlet/outlet water temperature under the standard heating condition of KS B 6275. The experimental data for the heat pump were measured using the air-enthalpy calorimeter and the constant temperature water bath. As the air-side temperature increases, the heating capacity and COP increase. The effect of the air-side relative humidities on the heat pump performance is insignificant. The heat pump performance on inlet and outlet water temperatures and air-side temperatures(-7, -11, -15℃) were studied. Heating capacity and COP increased about 27~39% with the air-side temperature increasing. Enthalpy between the front and the rear of condenser decreased about 6% by increasing of the inlet water temperature. These results can be utilized in the design of the air source heat pump system with air to water type.ties, and inlet/outlet water temperature under the standard heating condition of KS B 6275. The experimental data for the heat pump were measured using the air-enthalpy calorimeter and the constant temperature water bath. As the air-side temperature increases, the heating capacity and COP increase. The effect of the air-side relative humidities on the heat pump performance is insignificant. The heat pump performance on inlet and outlet water temperatures and air-side temperatures(-7, -11, -15℃) were studied. Heating capacity and COP increased about 27~39% with the air-side temperature increasing. Enthalpy between the front and the rear of condenser decreased about 6% by increasing of the inlet water temperature. These results can be utilized in the design of the air source heat pump system with air to water type.
Files in This Item
There are no files associated with this item.
Appears in
Collections
ETC > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE