공기열원 히트펌프의 난방 성능특성에 관한 실험적 연구Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type
- Other Titles
- Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type
- Authors
- 이권재; 권영철; 전종균; 박삼진; 권정태; 허철
- Issue Date
- 31-10월-2011
- Publisher
- 대한설비공학회 설비공학논문집
- Keywords
- Air to water; COP; Heating capacity; Heat pump; Performance
- Citation
- 설비공학논문집, v.23, no.6, pp 400 - 405
- Pages
- 6
- Journal Title
- 설비공학논문집
- Volume
- 23
- Number
- 6
- Start Page
- 400
- End Page
- 405
- URI
- https://www.kriso.re.kr/sciwatch/handle/2021.sw.kriso/7913
- Abstract
- This paper presents the heating performance characteristics of the air source heat pump
with air to water type. The heating capacity, COP, P-h diagram were measured at various
operating conditions, air-side temperatures, relative humidities, and inlet/outlet water
temperature under the standard heating condition of KS B 6275. The experimental data for
the heat pump were measured using the air-enthalpy calorimeter and the constant
temperature water bath. As the air-side temperature increases, the heating capacity and
COP increase. The effect of the air-side relative humidities on the heat pump
performance is insignificant. The heat pump performance on inlet and outlet water
temperatures and air-side temperatures(-7, -11, -15℃) were studied. Heating capacity and
COP increased about 27~39% with the air-side temperature increasing. Enthalpy between
the front and the rear of condenser decreased about 6% by increasing of the inlet water
temperature. These results can be utilized in the design of the air source heat pump
system with air to water type.ties, and inlet/outlet water
temperature under the standard heating condition of KS B 6275. The experimental data for
the heat pump were measured using the air-enthalpy calorimeter and the constant
temperature water bath. As the air-side temperature increases, the heating capacity and
COP increase. The effect of the air-side relative humidities on the heat pump
performance is insignificant. The heat pump performance on inlet and outlet water
temperatures and air-side temperatures(-7, -11, -15℃) were studied. Heating capacity and
COP increased about 27~39% with the air-side temperature increasing. Enthalpy between
the front and the rear of condenser decreased about 6% by increasing of the inlet water
temperature. These results can be utilized in the design of the air source heat pump
system with air to water type.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - ETC > 1. Journal Articles

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.