공기열원 히트펌프의 난방 성능특성에 관한 실험적 연구
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 이권재 | - |
dc.contributor.author | 권영철 | - |
dc.contributor.author | 전종균 | - |
dc.contributor.author | 박삼진 | - |
dc.contributor.author | 권정태 | - |
dc.contributor.author | 허철 | - |
dc.date.accessioned | 2023-12-22T07:31:11Z | - |
dc.date.available | 2023-12-22T07:31:11Z | - |
dc.date.issued | 2011-10-31 | - |
dc.identifier.uri | https://www.kriso.re.kr/sciwatch/handle/2021.sw.kriso/7913 | - |
dc.description.abstract | This paper presents the heating performance characteristics of the air source heat pump with air to water type. The heating capacity, COP, P-h diagram were measured at various operating conditions, air-side temperatures, relative humidities, and inlet/outlet water temperature under the standard heating condition of KS B 6275. The experimental data for the heat pump were measured using the air-enthalpy calorimeter and the constant temperature water bath. As the air-side temperature increases, the heating capacity and COP increase. The effect of the air-side relative humidities on the heat pump performance is insignificant. The heat pump performance on inlet and outlet water temperatures and air-side temperatures(-7, -11, -15℃) were studied. Heating capacity and COP increased about 27~39% with the air-side temperature increasing. Enthalpy between the front and the rear of condenser decreased about 6% by increasing of the inlet water temperature. These results can be utilized in the design of the air source heat pump system with air to water type.ties, and inlet/outlet water temperature under the standard heating condition of KS B 6275. The experimental data for the heat pump were measured using the air-enthalpy calorimeter and the constant temperature water bath. As the air-side temperature increases, the heating capacity and COP increase. The effect of the air-side relative humidities on the heat pump performance is insignificant. The heat pump performance on inlet and outlet water temperatures and air-side temperatures(-7, -11, -15℃) were studied. Heating capacity and COP increased about 27~39% with the air-side temperature increasing. Enthalpy between the front and the rear of condenser decreased about 6% by increasing of the inlet water temperature. These results can be utilized in the design of the air source heat pump system with air to water type. | - |
dc.format.extent | 6 | - |
dc.language | 한국어 | - |
dc.language.iso | KOR | - |
dc.publisher | 대한설비공학회 설비공학논문집 | - |
dc.title | 공기열원 히트펌프의 난방 성능특성에 관한 실험적 연구 | - |
dc.title.alternative | Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type | - |
dc.type | Article | - |
dc.publisher.location | 대한민국 | - |
dc.identifier.bibliographicCitation | 설비공학논문집, v.23, no.6, pp 400 - 405 | - |
dc.citation.title | 설비공학논문집 | - |
dc.citation.volume | 23 | - |
dc.citation.number | 6 | - |
dc.citation.startPage | 400 | - |
dc.citation.endPage | 405 | - |
dc.description.isOpenAccess | N | - |
dc.subject.keywordAuthor | Air to water | - |
dc.subject.keywordAuthor | COP | - |
dc.subject.keywordAuthor | Heating capacity | - |
dc.subject.keywordAuthor | Heat pump | - |
dc.subject.keywordAuthor | Performance | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
(34103) 대전광역시 유성구 유성대로1312번길 32042-866-3114
COPYRIGHT 2021 BY KOREA RESEARCH INSTITUTE OF SHIPS & OCEAN ENGINEERING. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.