Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

해수냉난방용 판형 열교환기의 최적설계를 위한 수치적 연구Numerical Study for the Optimal Design of Plate Heat Exchanger Using at Seawater Air Conditioning

Other Titles
Numerical Study for the Optimal Design of Plate Heat Exchanger Using at Seawater Air Conditioning
Authors
김현주정영권이호생윤정인손창효
Issue Date
30-8월-2014
Publisher
한국동력기계공학회
Keywords
plate heat exchanger; air conditioning system using seawater; j factor; f factor; numerical analysis
Citation
한국동력기계공학회, v.18, no.4, pp 29 - 35
Pages
7
Journal Title
한국동력기계공학회
Volume
18
Number
4
Start Page
29
End Page
35
URI
https://www.kriso.re.kr/sciwatch/handle/2021.sw.kriso/8000
Abstract
Plate heat exchanger are being applied in the field of OTEC (ocean thermal energy conversion) and SWAC (seawater air conditioning) system. This study is to analyze numerically the heat transfer and pressure drop characteristics by using solid works flow simulation in order to offer optimum design data of plate heat exchanger. Plater heat exchanger proposed in this study is four types. The geometric design parameters of plate heat exchanger are a channel space, a flow orientation, a plate array, the flowrate of working fluid and so on. The main results for numerical analysis of plate heat exchangers are summarized as follows. Heat transfer performance for the channel space of 2.4 mm shows the highest value compared to other spaces. And, the 4-type plate heat exchanger in Table 2 is the highest performance. From the pressure drop characteristics of plate heat exchanger, the channel space of 3.2 mm shows the lowest value. And 1-type plate heat exchanger in Table 2 is the lowest pressure drop.id works flow simulation in order to offer optimum design data of plate heat exchanger. Plater heat exchanger proposed in this study is four types. The geometric design parameters of plate heat exchanger are a channel space, a flow orientation, a plate array, the flowrate of working fluid and so on. The main results for numerical analysis of plate heat exchangers are summarized as follows. Heat transfer performance for the channel space of 2.4 mm shows the highest value compared to other spaces. And, the 4-type plate heat exchanger in Table 2 is the highest performance. From the pressure drop characteristics of plate heat exchanger, the channel space of 3.2 mm shows the lowest value. And 1-type plate heat exchanger in Table 2 is the lowest pressure drop.
Files in This Item
There are no files associated with this item.
Appears in
Collections
친환경해양개발연구본부 > 해수에너지연구센터 > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Ho saeng photo

Lee, Ho saeng
친환경해양개발연구본부 (해수에너지연구센터)
Read more

Altmetrics

Total Views & Downloads

BROWSE