다양한 냉매를 적용한 내부열교환기 부착 2단 압축 냉동시스템의 성능 분석

Full metadata record
DC Field Value Language
dc.contributor.author윤정인-
dc.contributor.author허성관-
dc.contributor.author제재면-
dc.contributor.author전민주-
dc.contributor.author손창효-
dc.contributor.author문정현-
dc.date.accessioned2023-12-22T07:31:01Z-
dc.date.available2023-12-22T07:31:01Z-
dc.date.issued2015-
dc.identifier.issn2713-8429-
dc.identifier.issn2713-8437-
dc.identifier.urihttps://www.kriso.re.kr/sciwatch/handle/2021.sw.kriso/7879-
dc.description.abstractIn this paper, cycle performance analysis of two-stage compression and one-stage expansion refrigeration system applied various refrigerants is presented to offer the basic design data for the operating parameters of the system. The operating parameters considered in this study include degree of superheating and subcooling, compressor efficiency, evaporation temperature, condensing temperature, mass flow rate ration into inter-cooler, effectiveness of internal heat exchanger. The main results were summarized as follows : The COP of two-stage compression and 1-stage expansion refrigeration system increases with the increasing subcooling, mass flow rate ration of inter-cooler, evaporation temperature, but decreases with the increasing condensing temperature and superheating degree. Therefore, subcooling degree, mass flow rate ratio of inter-cooler of two-stage compression and 1-stage expansion using substitute refrigerant have an effect on COP of this system. The COP of alternative refrigerants was higher than the COP of R22 in this study, although the COP of some mixed refrigerants were lower than COP of R22.-
dc.format.extent7-
dc.language한국어-
dc.language.isoKOR-
dc.publisher한국동력기계공학회-
dc.title다양한 냉매를 적용한 내부열교환기 부착 2단 압축 냉동시스템의 성능 분석-
dc.title.alternativePerformance Analysis of Two-stage Compression Refrigeration System with Internal Heat Exchanger Applied Various Refrigerants-
dc.typeArticle-
dc.publisher.location대한민국-
dc.identifier.doi10.9726/kspse.2015.19.6.082-
dc.identifier.bibliographicCitation동력시스템공학회지, v.19, no.6, pp 82 - 88-
dc.citation.title동력시스템공학회지-
dc.citation.volume19-
dc.citation.number6-
dc.citation.startPage82-
dc.citation.endPage88-
dc.identifier.kciidART002065573-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorTwo-stage compression and one-stage expansion refrigeration system-
dc.subject.keywordAuthorAlternative refrigerant-
dc.subject.keywordAuthorInternal heat exchanger-
dc.subject.keywordAuthorCOP-
dc.subject.keywordAuthorMass flow-rate-