60RT급 해수냉난방시스템의 성능특성에 관한 실험적 연구
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 이호생 | - |
dc.contributor.author | 정동호 | - |
dc.contributor.author | 김현주 | - |
dc.date.accessioned | 2021-12-08T18:40:26Z | - |
dc.date.available | 2021-12-08T18:40:26Z | - |
dc.date.issued | 20120531 | - |
dc.identifier.uri | https://www.kriso.re.kr/sciwatch/handle/2021.sw.kriso/5300 | - |
dc.description.abstract | This study experimented on a heating and cooling system that uses the deep ocean water as a heat source in a laboratory equipped with the water intake system. Experiments on direct cooling using the deep ocean water of yearlong temperatures at 5 oC or less were performed. Experiments on heating using a heat pump system were performed with various ocean waters as heat sources including the deep ocean water at 5 oC, the surface ocean water at 10 oC, and the ground ocean water at 13 oC, among others. The comparison results between the conventional cooling systems and the direct cooling system using the deep ocean water revealed that the latter saved approximately 75.6% of the TOE and reduced the carbon dioxide exhaust by about 1.45 tCO2. The heating COPs of the surface ocean water and the ground ocean water increased by approximately 2.9% and 8.4% more, respectively, than that of the deep ocean water.ures at 5 oC or less were performed. Experiments on heating using a heat pump system were performed with various ocean waters as heat sources including the deep ocean water at 5 oC, the surface ocean water at 10 oC, and the ground ocean water at 13 oC, among others. The comparison results between the conventional cooling systems and the direct cooling system using the deep ocean water revealed that the latter saved approximately 75.6% of the TOE and reduced the carbon dioxide exhaust by about 1.45 tCO2. The heating COPs of the surface ocean water and the ground ocean water increased by approximately 2.9% and 8.4% more, respectively, than that of the deep ocean water. | - |
dc.language | 한국어 | - |
dc.language.iso | KOR | - |
dc.title | 60RT급 해수냉난방시스템의 성능특성에 관한 실험적 연구 | - |
dc.title.alternative | An Experimental Study for Performance Characteristics of 60RT Seawater Air-Conditioning System | - |
dc.type | Conference | - |
dc.citation.title | 한국해양공학회 2012 춘계학술대회 | - |
dc.citation.volume | 1 | - |
dc.citation.number | 1 | - |
dc.citation.startPage | 1670 | - |
dc.citation.endPage | 1675 | - |
dc.citation.conferenceName | 한국해양공학회 2012 춘계학술대회 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
(34103) 대전광역시 유성구 유성대로1312번길 32042-866-3114
COPYRIGHT 2021 BY KOREA RESEARCH INSTITUTE OF SHIPS & OCEAN ENGINEERING. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.